Snow Melt Recommended Specifications
Download the PDF version.
Part
1 - General
Furnish and install an engineered surface
snowmelt system complete with layout drawings, UL Listed heating
cable and components and control panel with snow sensor and
ground fault protection equipment. Heating cable must be suitable
for direct burial in concrete or asphalt. The heat tracing system shall
conform to IEEE Standard 515.1. Comply with manufacturer’s installation
instructions in its entirety.
Part 2 - Products
-
The heating cable and termination components shall be UL
Listed specifically as electric de-icing and snow-melting
equipment.
-
The heating cable shall be of parallel resistance construction
capable of being cut-to-length and terminated in the field.
Series resistance, constant wattage cables or mats shall
not be allowed.
-
The cable shall provide the heat necessary to melt snow
and ice through a power limiting coiled resistor alloy
element helically wound around two (2) fluoropolymer insulated
12 AWG stranded nickel-plated copper bus conductors. The
heater will be covered by a fluoropolymer dielectric jacket,
fiberglass cushion braids for impact resistance, a nickel-plated
copper braid for grounding purposes and an overall silicone
outer jacket for added protection during installation.
-
The heating cable must reduce power output at elevated
temperatures to prevent overheating and system damage if
accidentally energized during ambient temperatures exceeding
400F. Heating cable must be of the power-limiting
type so as not to require circuit breaker oversizing as
is required when using self-regulating type cables.
-
The cable must avoid elevated cold start currents at temperatures
below +500F that would require oversizing power distribution
and circuit breakers. Heating cables that exhibit
high in-rush current shall not be allowed.
-
The heater shall operate on a line voltage of (select
208, 240, 277 or 480) Vac without the use of transformers. Voltage
rating of the dielectric insulation shall be 600 Vac.
-
Power connections and end seal terminations shall be made
in junction boxes as described under Part 6, Installation. Power
connections and end seal terminations are not to be buried
in concrete or asphalt.
-
Acceptable products and manufacturers: SMB™ Power
Limiting Heating Cable as manufactured by Bylin Engineered
Systems, El Dorado Hills, CA (1-888-313-5666)
Part 3 - Power Distribution and Control The control system shall include a remote snow sensor located
outdoors in accordance with manufacturer's instructions
and control panel containing branch circuit breakers, ground
fault protection, contactors, power on light and an auto,
on, off control switch.
The
control system shall be custom engineered and supplied
by Bylin Engineered Systems, El Dorado Hills, CA, (1-888-313-5666).
Part 4 - System Performance
-
Heating cable spacing shall be based on (select a, b, c
or d design method listed below):
-
Manufacturer’s snow melting design guide for
a (select: non-critical or critical area) with (select:
light, moderate or heavy) snowfall level.
-
Chapter 45, Snow Melting, of the ASHRAE Handbook utilizing
data for the city of __________________________________. Design
shall meet the (insert percentage) level of clear
surface under normal snowfall conditions per
Table 1.
-
Section 6.3,
Snow Melting, of the IEEE Standard 515.1 – 1995
Recommended Practice for the Testing, Design, Installation
and Maintenance of Electrical Resistance Heat Tracing
for Commercial Applications.
-
30 wts/ft2 based on heating cable
power output during steady state snowmelting
conditions. The
design shall not be based on startup or cable
inrush characteristics.
-
System
performance shall be based on heated surface
temperatures of 320F (minimum) during the snow melting
process. Start
up in cold concrete shall be used for circuit
breaker sizing only
Part 5 - Supplier
- The supplier shall demonstrate experience designing
and engineering snow and ice melting systems and shall
have at least 10 years experience in the custom engineering,
design and supply of complete surface snowmelt systems. The
supplier shall be Bylin Engineered Systems, El Dorado Hills, CA (1-888-313-5666).
Part 6 - Installation
-
Heating cable shall be installed:
a) Concrete--Poured in place within 2”-4” of
the finished surface.
b) Asphalt--Embedded in asphalt within
1”-2” of
the finished surface.
c) Pavers--Installed in the sand bed below the finished
paver surface.
-
Installer shall follow
supplier's installation instructions and design guide
for proper installation and layout methods.
-
Power connections
and end seal terminations shall be located in Nema 4
or 4X junction boxes. The heating cable located
between the junction boxes and concrete shall be encased
in rigid metal conduit (with protective bushings at each
end) that extend 12” into the concrete, asphalt or
substrate.
-
Contractor shall provide and install: power wiring
to the control panel, from the control panel to the
heating circuit power termination boxes and from
the snow sensor to the control panel. Locate the
automatic snow detector sensor as indicated on systems
drawings provided by the supplier.
-
All installations and
terminations must be made to conform to the NEC and
any applicable other national or local code requirements.
-
Circuit
breakers supplying power to the heat tracing must be
equipped with 30 mA minimum ground-fault equipment protection
or equivalent ground fault protection system (5mA
GFCI shall not be used as nuisance tripping may result).
Part 7 - Testing
-
Heating cable should be tested with a 2,500 Vdc megohmeter
(megger) between the heating cable bus wires and the heating
cable’s metallic braid. While
a 2,500 Vdc megger test is recommended, the minimum acceptable level for testing
is 1,000 Vdc. This test should be performed a minimum of four times:
-
While the cable is still on the reel, prior to installation;
-
After installation of cable and completion of circuit
fabrication kits but prior to concrete, asphalt or
paver placement.
-
During the placement of concrete, asphalt or pavers.
(ABSOLUTE REQUIREMENT!)
Note: Should the cable be damaged during the concrete pour, the pour shall stop,
the electrician and concrete foreman shall locate the damaged cable, repair the
cable with an approved splice kit, reinstall the cable on the rebar or wire grid,
retest the repaired cable before the concrete pour can continue.
-
Upon completion of placement of concrete or asphalt.
-
The minimum acceptable level for the megger readings
is 20 megohms, regardless of the circuit length.
-
The Construction
Manager for the project or authorized representative
should witness megger tests. Results of the megger readings
should be recorded and submitted to the Construction Manager.
|